LFUCG Town Branch 22 MG Wet Weather Flow Storage & 56 MGD Pumping Facilities

  • LFUCG Town Branch 22 MG Wet Weather Flow Storage & 56 MGD Pumping Facilities, Lexington, KY

  • LFUCG Town Branch 22 MG Wet Weather Flow Storage & 56 MGD Pumping Facilities, Lexington, KY

  • LFUCG Town Branch 22 MG Wet Weather Flow Storage & 56 MGD Pumping Facilities, Lexington, KY

  • LFUCG Town Branch 22 MG Wet Weather Flow Storage & 56 MGD Pumping Facilities, Lexington, KY

  • LFUCG Town Branch 22 MG Wet Weather Flow Storage & 56 MGD Pumping Facilities, Lexington, KY

Lexington’s 22 MG wet weather storage tank is an above grade, pre-stressed concrete structure. It has an overflow weir box and a four-plex submersible pumping station that conveys peak wet weather flows to the tank. The tank has a diameter of 260 feet and a side water depth of 55 feet.

GRW provided design, bidding, and construction phase services for the project.

When flow to the treatment plant exceeds 70 MGD, an electrically actuated modulating gate restricts flow to the treatment facilities. Excess flow diverts by gravity to the wet weather storage facility pump station through another electrically actuated gate. Three variable frequency drive operated pumps work to maintain a constant level in the wetwell, transferring flow into storage. 

Once the event has passed and flow to the treatment plant has dropped to 60 MGD, an electrically actuated plug valve initiates gravity return of flow from storage to maintain 70 MGD maximum to the treatment facilities. 

This project is considered Phase 1 for wet weather management in this area of Lexington’s sanitary sewer system; ultimately, a 44-million gallon storage facility is planned for the site.